Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

Overview

The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.

Technical Summary

Units:
Rating Range 120 to 600V, single phase and three phase @ 50/60 Hz 120 to 600V, single phase and three phase @ 50/60 Hz Less
Transfer Type Switch application dependent Switch application dependent Less
Switch Type Switch application dependent Switch application dependent Less

ATC Controller Specifications

Input control voltage 65 to 145 Vac 50/60 hZ 65 to 145 Vac 50/60 hZ Less
Voltage measurements of Utility Source 1 VAB Source 2 VAB
Source 1 VAC Source 2 VBC
Source 1 VCA Source 2 VCA
Source 1 VAB Source 2 VAB
Source 1 VAC Source 2 VBC
Source 1 VCA Source 2 VCA
Less
Voltage measurement range 0 to 790 VAC rms (50/60 Hz) 0 to 790 VAC rms (50/60 Hz) Less
Voltage measurement accuracy +/-2% of nominal input voltage +/-2% of nominal input voltage Less
Frequency measurements of Source 1 and Source 2 Source 1 and Source 2 Less
Frequency measurement range 40 Hz to 70 Hz 40 Hz to 70 Hz Less
Frequency measurement accuracy +/- 0.1 Hz +/- 0.1 Hz Less
Undervoltage dropout 50% to 90% of nominal voltage 50% to 90% of nominal voltage Less
Undervoltage pickup (Dropout +2%) to 99% of the nominal system voltage (Dropout +2%) to 99% of the nominal system voltage Less
Underfrequency dropout range 90 to 97% of the nominal system frequency 90 to 97% of the nominal system frequency Less
Underfrequency pickup range (Dropout +1 Hz) to 99% of the nominal system frequency (Dropout +1 Hz) to 99% of the nominal system frequency Less
Overfrequency dropout range 103 to 110% of the nominal system frequency 103 to 110% of the nominal system frequency Less
Overfrequency pickup range 101% to (dropout - 1 Hz) of the nominal system frequency 101% to (dropout - 1 Hz) of the nominal system frequency Less
Operating temperature range -20 to 70 degree C (-4 to +158 degree F) -20 to 70 degree C (-4 to +158 degree F) Less
Storage temperature range -30 to 85 degree C (-22 to +185 degree F) -30 to 85 degree C (-22 to +185 degree F) Less
Operating humidity 0 to 95% relative humidity (noncondensing) 0 to 95% relative humidity (noncondensing) Less
Operating environment Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons Less
Generator start relay 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load Less
K1, K2 relays
10A, 1-3 hp @ 250 Vac

10A@30 Vdc

10A, 1-3 hp @ 250 Vac

10A@30 Vdc
Less
Applicable testing UL-recognized component
Meets intent of UL 991 & UL 1008
Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
UL-recognized component
Meets intent of UL 991 & UL 1008
Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
Less
Applicable testing continued 1000-4-5, 1000-4-6, 1000-4-11
CISPR 11, Class A
FCC Part 15, Class A
CSS 22.2-178
1000-4-5, 1000-4-6, 1000-4-11
CISPR 11, Class A
FCC Part 15, Class A
CSS 22.2-178
Less
Enclosure compatibility NEMA 1, NEMA 3R and NEMA 12
UV-resistant ATC-300+ faceplate
NEMA 1, NEMA 3R and NEMA 12
UV-resistant ATC-300+ faceplate
Less

Product Features

  • Auxiliary relay contacts:
    • Source 1 present 2NO and 2NC
    • Source 2 present 2NO and 2NC

  • Source 1 and source 2 sensing:
    • Undervoltage / underfrequency
    • Overvoltage / overfrequency
    • Three-phase rotation protection
    • Three-phase voltage unbalance/loss

  • Pre-transfer signal contacts 1NO and 1NC
  • Go to emergency (Source 2)
  • Seven field-programmable time delays
  • LCD-based display for programming, system diagnostic and help message display
  • Mimic diagram with source available and connected LED indication
  • Time-stamped history log
  • System test pushbutton
  • Programmable plant exercise (off, daily, 7,14 and 28 day) interval selectable run time 0-600 minutes no load/load with fail-safe
  • Integral overcurrent protection (optional)
  • In-phase transition
  • Stainless steel cover for controller (optional)
  • Communications via RS-232 or Modbus through an integrated RS-485 port (optional)