< Back

  • 2000 to 3000 ekW, 2500 to 3750 kVa
  • 50 Hz 1500 RPM or 60 Hz 1800 RPM
  • 380 to 13800 Volts
  • For Standby, Prime and Continuous applications
Biogas Project Financing
See our Offers
View Product Downloads
Please answer to continue. Select an option to continue. Enter a valid email address.
Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

Overview

From natural gas-fueled combined heat and power (CHP) systems and emergency power for facilities, to renewable biogas energy to support the local grid, or electricity generated from coal mine gases, Caterpillar has a wide range of reliable gas power solutions.

Gas Generator Sets Specification

Units:
Maximum Continuous Rating 1560kW 1560kW Less
Fuel Type Natural Gas, Biogas, Coal Gas Natural Gas, Biogas, Coal Gas Less
Maximum Electrical Efficiency 43.3% 43.3% Less
Maximum Standby Rating - - Less
Frequency 50/60Hz 50/60Hz Less
rpm 1500rpm 1500rpm Less

Engine Specification

Engine Model CG170 CG170 Less
Bore 6.7 in 170.0 mm Less
Stroke 7.7 in 195.0 mm Less
Displacement 4320.0 in3 70.8 L Less
Aspiration TA TA Less

Generator Set Dimension

Length 261.4168 in 6640.0 mm Less
Width 70.0 in 1778.0 mm Less
Height 87.0 in 2210.0 mm Less
Dry weight genset 32848.54 lb 14900.0 kg Less

CG170-16 Standard Equipment

Air Inlet
  • Two-element single-stage air cleaner with enclosure and service indicator
  • Turbocharger for the CG132-8 with a water-cooled bearing case

Control Panels
  • TEM(Total Electronic Management)

Cooling
  • Jacket water and SCAC thermostats
  • Cat flanges on SCAC circuit
  • Electrical jacket water and aftercooler coolant pump
  • flange connections for JW inlet and outlet

Exhaust
  • Closed crankcase ventilation system
  • PEARL/Low resistence exhaust system

Cooling
  • Engine driven water pumps for jacket water and aftercooler
  • Jacket water and SCAC thermostats
  • ANSI/DN customer flange connections for JW inlet and outlet
  • Cat flanges on SCAC circuit

Fuel system
  • Electronic fuel metering valve
  • Pre-chamber spark plugs
  • Independently controlled cylinder monitoring and ignition system

Generator
  • Reactive droop
  • Bus bar connections
  • Winding temperature detectors
  • Anti-condensation space heater
  • 3-phase sensing and KVAR/PF control

Starting/Charging
  • 24V starting motors
  • Battery disconnect switch

General
  • Crankshaft vibration damper and guard

CG170-16 Optional Equipment

Air Inlet
  • Mounting stand
  • Air cleaner with preleaner

Cooling
  • CHP skid