Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

Overview

This fuel-optimized rental power product is ideal for customers interested in consuming the least amount of fuel. Each model delivers increased flexibility by easily switching between 50 and 60 Hz, which allows one machine to satisfy varying load requirements across diverse regions and applications including mining, manufacturing, oil and gas and construction.

Generator

Units:
Rating 300 kVA Prime 300 kVA Prime Less
Frequency 50/60 Hz 50/60 Hz Less
Voltage 127 - 480 V 127 - 480 V Less

Engine

Engine C9 ACERT Diesel Engine (BSFC) C9 ACERT Diesel Engine (BSFC) Less
Fuel Diesel Diesel Less

Dimensions

Width 55.0 in 1400.0 mm Less
Height 84.0 in 2124.0 mm Less
Length 160.0 in 4065.0 mm Less
Weight 8553.0 lb 3880.0 kg Less

Fuel / Emissions Strategy

• Best Fuel efficiency

Single-source Supplier

• Factory designed and fully prototype tested with certified torsion vibration analysis available

Cat C9 ACERT Diesel Engine

• Four-stroke diesel engine combines performance and excellent fuel economy with minimum weight

Cat EMCP 4.2B Control Panel

• Fully featured power metering, protective relaying, and engine/generator control and monitoring

Optional Cat EMCP 4.4 Control Panel

• Synchronising capabilities

Cat LC5100 Generator

• Designed to match performance and output characteristics of Cat diesel engines

Integrated Voltage Regulator (IVR)

• Three-phase sensing

Enclosure

• Galvanized sheet steel construction

Rear Customer Access

• Sound isolated control panel with integrated power distribution access

Reduced Environmental Impact

• High Fuel efficiency

XQP300 Standard Equipment

Air Inlet
  • Air cleaner, cyclonic/paper with dust cup and service indicator

Charging System
  • 230V, 5A battery charger, enclosed in dust-proof housing

Control Panel
  • EMCP 4.2B generator set mounted digital controller

Cooling System
  • Variable speed pusher fan

Distribution System
  • Separate load and control sections

Enclosure
  • Sound attenuating, galvanized sheet metal enclosure limits overall noise

Engine
  • Cat C9 ACERT heavy duty diesel engine

Exhaust System
  • Integrated spark arresting silencer with flexible connectors, in separate compartment

Fuel System
  • Single wall tank – usable volume 157 gal (593 L); run time @ 75% prime load: 11.3 hours

Generator
  • LC5100 series, three-phase, random wound, 12-lead design, self-excited, 2/3 pitch

Lube System
  • On-engine primary and secondary oil filters, filler, and dipstick

Mounting System
  • Generator set soft mounted to the heavy duty, fabricated steel base frame

Starting System
  • Single electric starting motor, 24V