Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

Overview

The 150 kVA model comes in two versions. The Stage IIIA product is emission-optimized and legally required on all mobile applications in Europe, while the fuel-optimized product is ideal for customers interested in consuming the least amount of fuel. Each model delivers increased flexibility by easily switching between 50 and 60 Hz, which allows one machine to satisfy varying load requirements across diverse regions and applications including mining, manufacturing, oil and gas and construction.

Generator

Units:
Rating 150 kVA Prime 150 kVA Prime Less
Frequency 50/60 Hz 50/60 Hz Less
Voltage 127 - 408 V 127 - 408 V Less

Engine

Engine C7.1 Diesel Engine C7.1 Diesel Engine Less
Fuel Diesel Diesel Less

Dimensions

Width 44.1 in 1120.0 mm Less
Height 87.6 in 2226.0 mm Less
Length 138.6 in 3520.0 mm Less
Weight 5615.0 lb 2547.0 kg Less

Fuel / Emissions Strategy

Meets Stage IIIA emissions standards

Single-source Supplier

• Factory designed and fully prototype tested with certified torsional vibration analysis available

Cat C7.1 Diesel Engine

• Four-stroke diesel engine combines consistent performance and excellent fuel economy with minimum weight

Cat EMCP 4.2B Control Panel

• Fully featured power metering, protective relaying, and engine/generator control and monitoring

Cat LC3100 Generator

• Designed to match performance and output characteristics of Cat diesel engines

Integrated Voltage Regulator (IVR)

• Three-phase sensing

Enclosure

• Galvanized sheet steel construction

Reduced Environmental Impact

• Meets Stage IIIA emissions standards

Rental-ready Features

• Forklift pockets

Available Options

• CE socket box with integrated MCB and RCBO protection

XQP150 Standard Equipment

Air Inlet
  • Air cleaner, two stage cyclonic/paper with dust cup and service indicator

Alternator
  • LC3114J frame — 3-phase, random wound, 12 lead design, self excited, 2/3 pitch

Charging System
  • Charging alternator — 12V, heavy duty with integral regulator and belt guards

Control Panel
  • EMCP 4.2B generator set mounted digital controller

Cooling System
  • Package-mounted radiator with high ambient performance

Distribution System
  • Robust steel enclosure, separate hinged, lockable door with rust-resistant pinned hinges

Enclosure
  • Sound attenuating, galvanized sheet metal enclosure with exceptional noise reduction performance

Engine
  • Cat C7.1 heavy-duty diesel engine

Exhaust System
  • Integrated spark arresting silencer with flexible connectors, in separate compartment

Fuel System
  • 156 gal (590 L) double-wall fuel tank, 24-hour runtime @ 75% prime rating, internal fuel fill

Generator
  • LC3114J frame, three-phase, random wound, 12-lead design, self-excited, 2/3 pitch

Lube System
  • On-engine primary and secondary oil filters, filler, and dipstick

Mounting System
  • Generator set soft-mounted using captive vibration mounts

Starting System
  • Single electric starting motor, 12V

General
  • Factory testing of standard generator set