< Back

View Product Downloads
Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

C4.4 (60 Hz) Standard Equipment

Charging System
  • CAT Premium High Output Battery(s) with rack & cables Installed (wet);1000CCA;90amp hr;12V

Control System
  • EMCP 4.2
  • Controls include: Run / Auto / Stop Control - Speed Adjust - Engine Cycle Crank - Emergency Stop pushbutton
  • Features include: 12-volt DC operation - Environmental sealed front face - Text alarm/event descriptions
  • Digital indators for: RPM - DC volts - Operating hours, - Oil pressure - Coolant pressure - Volts (L-L & L-N), frequency (Hz) - Amps (per phase & average) - Power Factor (per phase & average) - kW (per phase,average & percent) - kVA (per phase,average & percent) - kVAr (per phase,average & percent) - kW-hr (total) - kVAr-hr (total)
  • Warning / Shutdown with common LED indicators for: -Low Oil pressure - Low coolant temperature alarm (detects jkt water heater failure) - High coolant temperature shutdown
  • Communications: Customer DATA link (Modbus RTU) - RS485 Serial DATA link (terminals only) - 8 programmable digital outputs available - 2 relays pre-programmed - 8 programmable digital inputs available - 2 pre-programmed

Circuit Breakers
  • Optional UL/CSA listed mainline breakers
  • Optional Multiple Breakers 100% Rated 3-pole with solid neutral
  • NEMA 1 steel enclosure
  • Electrical stub-up area directly below circuit breaker

Cooling System
  • Radiator and cooling fan complete with protective guards
  • Standard ambient temperatues up to 50degC (122degF)
  • 50% coolant antifreeze/corrosion inhibitor
  • Coolant reservoir

Generator
  • Insulation system,class H
  • Drip proof generator air intake (NEMA 2,IP23)
  • Electrical design in accordance with BS5000 Part 99,EN61000-6, IEC60034-1,NEMA MG-1.33
  • All electroplated hardware or stainless steel
  • Anticorrosive paint protection
  • High gloss polyurethane paint for durability and scuff resistance

Mounting System
  • Heavy-duty fabricated steel base with lifting points
  • Anti-vibration pads to ensure vibration isolaton
  • Complete OSHA guarding
  • Stub-up pipe ready for connection to silencer pipework
  • Flexible fuel lines to base with NPT connections

General
  • Warranty per SELF5611

C4.4 (60 Hz) Optional Equipment

Certificates
  • IBC Seismic and Wind Certifications

Air Inlet System
  • Cartridge type air filter

Charging System
  • NFPA battery charger UL10A 120VAC

Circuit Breakers
  • 3-Pole 100% rated
  • Breakers (100% UL rated)
  • Second circuit breaker box
  • Power perminal strips

Control Panels
  • NFPA110 bundle includes: FSS low fuel level alarm & indication panel circuitry required when sub-base tank is selected - WSS1 Low Coolant level shut down - WCA1 Low Coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA Battery Charger - A coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application
  • Oil temperature guage and sender
  • Audible alarm
  • Ground fault relay
  • Discrete I/O module
  • Remote E-stop button
  • Volt free contacts genset run and common alarm
  • Remote annunciator
  • Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker

Cooling System
  • Radiator stone guard
  • Radiator transition flange

Enclosures
  • Weatherproof enclosure
  • Sound attenuated enclosure, level 1
  • Sound attenuated enclosure, level 2
  • Panel viewing window
  • External emergency stop

Heating Elements
  • Coolant heater
  • Jacket water heater
  • Anti-condensation heater
  • Battery heater
  • Lube oil sump heater
  • Wiring for canopy space heater

Exhaust System
  • 10, 25 and 35 dBA silencer systems
  • Overhaed silencer mounting kit

Fuel System
  • 209 and 394 gallon sub-base fuel tanks
  • 5 gallon fill containment
  • 5 gallon spill containment
  • Emergency vent pipe
  • Tank riser

Generators
  • Permanent magnet generator

Mounting System
  • Seismic vibration isolators

Tests
  • Generator test report
  • PGS test report @ 1.0 power factor
  • PGS test report @ 0.8 power factor
  • 4 Hour factory test

Overview

Producing reliable power from 36 ekW to 60 ekW at 60Hz, our C4.4 diesel generator sets are engineered to meet your standby and prime applications, and measure up to your power standards. All are tested to maximum load before they leave any one of our ISO 9001 certified facilities. And because we believe power is more than quantity of kilowatts but quality of performance, we've incorporated our common rail fuel system for improved fuel efficiency, designed to meet EPA Stationary Emergency (Tier 3) emissions standards. Seismic certification is also available to maintain power during unexpected disturbances. Our integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. The EMCP 4.2 control panel, with a user-friendly interface, puts our advanced management and diagnostic tools in one. No two power needs are alike, which is why we offer a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging options to work with your spatial and environmental conditions. It's already built to exceed your expectations — customize your C4.4 generator sets to meet your demands.

Generator Set Specifications

Units:
Minimum Rating 36 ekW 36 ekW Less
Maximum Rating 60 ekW 60 ekW Less
Voltage 208-600 Volts 208-600 Volts Less
Frequency 60 Hz 60 Hz Less
Speed 1800 RPM 1800 RPM Less
Height - Maximum 53.6 in 1361.0 mm Less
Length - Maximum 75.8 in 1925.0 mm Less
Width - Maximum 44.1 in 1120.0 mm Less

Generator Set Configurations

Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency Use Only (Tier 3 Nonroad Equivalent Emission Standards) U.S. EPA Certified for Stationary Emergency Use Only (Tier 3 Nonroad Equivalent Emission Standards) Less

Engine Specifications

Engine Model C4.4, In-line 4, 4-cycle diesel C4.4, In-line 4, 4-cycle diesel Less
Compression Ratio 18.2:1 18.2:1 Less
Governor Type Adem™A4 Adem™A4 Less
Fuel System Electronic (adjustable) Electronic (adjustable) Less
Bore 4.13 in 105.0 mm Less
Displacement 268.5 in 4.4 l Less
Stroke 5.0 in 127.0 mm Less

Design Criteria

  • The generator set is designed to meet ISO8528-5 transient response and NFPA 110.
  • Cooling system designed to operate in 50˚C / 122˚F ambient temperatures with an air flow restriction of 0.5 in. water.
  • Single-Source Supplier

    Fully prototype tested with certified torsional vibration analysis available

    CE Certification

    CE Certification available

    World Wide Product Support

    Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

    General

  • Single wall 8 hour wide fuel tank
  • Circuit breaker, IEC, 3 pole
  • Industrial Silencer (10dBA)