The ATC-800 Controller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-800's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.
The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-800 to meet the particular application. The ATC-800 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.
Input Control Voltage | 120Vac (50/60 Hz) (operating range 65 to 160 Vac) 120Vac (50/60 Hz) (operating range 65 to 160 Vac) | More |
Voltage Measurements of Utility | Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System) Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System) |
More |
Voltage Measurement Range | 0 to 700 Vac 0 to 700 Vac | More |
Voltage Measurement Accuracy | +/-1% of full scale +/-1% of full scale | More |
Frequency Measurements Of | Source 1 and Source 2 Source 1 and Source 2 | More |
Frequency Measurement Range | 40 Hz to 80 Hz 40 Hz to 80 Hz | More |
Frequency Measurement Accuracy | +/- 0.1 Hz +/- 0.1 Hz | More |
Undervoltage Dropout | Breaker Style 50 to 97% of Nominal System Voltage Contactor Style - 78 to 97% Breaker Style 50 to 97% of Nominal System Voltage Contactor Style - 78 to 97% |
More |
Undervoltage Pickup | (Dropout +2%) to 99% of Nominal System Voltage (Dropout +2%) to 99% of Nominal System Voltage | More |
Underfrequency Dropout Range | 90 to 97% of Nominal System Frequency 90 to 97% of Nominal System Frequency | More |
Underfrequency Pickup Range | (Dropout +1 Hz) to 99% of Nominal System Frequency (Dropout +1 Hz) to 99% of Nominal System Frequency | More |
Overfrequency Dropout Range | 103 to 110% of Nominal System Frequency 103 to 110% of Nominal System Frequency | More |
Overfrequency Pickup Range | 101% to (Dropout +1 Hz) of nominal system frequency 101% to (Dropout +1 Hz) of nominal system frequency | More |
Operating Temperature Range | -20 to 70 degree C (-4 to +158 degree F) -20 to 70 degree C (-4 to +158 degree F) | More |
Operating Humidity | Up to 90% Relative Humidity (non-condensing) Up to 90% Relative Humidity (non-condensing) | More |
Enclosure Compatibility | More |
System Voltage Application | 120 to 600 Vac (50/60 Hz) (single or three phase) 120 to 600 Vac (50/60 Hz) (single or three phase) | More |
Factory programming will load all standard features and customer-specified options per the default settings.
In-phase monitor is a feature that will allow a transfer between two sources only when the phase difference between the two sources is near zero. This is an open transition transfer that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Load voltage decay transfer is a feature that, after opening the switch for the original source, holds in the neutral position until the voltage on the load is less than 30% of rated voltage. This operation is an open transition that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Caterpillar offers a comprehensive variety of electric power systems, customised to fit your needs. Our specialised systems deliver high power and performance in industries across the globe. With Caterpillar, you get outstanding manufacturing quality, expert support, and the essential tools and applications to complete any project.
Learn More About Electric PowerCat generator sets provide a complete factory-built solution with fully featured standard and advanced controls. Optional accessories enhance the capabilities of the genset package-mounted control system.
Learn MoreExplore valuable resources for generator sizing, specification, and training materials. SpecSizer evaluates load types, collects data, and organises it to help you select the generator set that's best for you. Find product comparisons, technical data, product sizing, and more using our technical information portal (TIP) specifically created for consultants, architects, engineers, and owners.