The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.
Communications Interface - Optional | Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) | More |
Control Power | 120 VAC 120 VAC | More |
Delay NeutralTransition Time Delays (DT,DW) | 0-10 minutes 0-10 minutes | More |
Delay Transfer to Nonpreferred Source (W) | 0-5 minutes 0-5 minutes | More |
Delay for Engine Cool Down (U) | 0-60 minutes 0-60 minutes | More |
Load Control Relay Contacts (1) | rated for 10A @ 24VDC or 120VAC rated for 10A @ 24VDC or 120VAC | More |
Load Control Relay Contacts (2) | 0-259 minutes 0-259 minutes | More |
Operating Temperature Ambient | (-20˚C to 50˚C) (-20˚C to 50˚C) | More |
Overfrequency Dropout for Source 1 and Source 2 | 50.1 - 63 Hz 50.1 - 63 Hz | More |
Overfrequency Restore for Source 1 and Source 2 | 50 - 62.9 Hz 50 - 62.9 Hz | More |
Overvoltage Dropout for Source 1 and Source 2 | 105 - 110% of nominal 105 - 110% of nominal | More |
Overvoltage Restore for Source 1 and Source 2 | 103 - 108% of nominal 103 - 108% of nominal | More |
Source Sensing | 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) | More |
Storage Temperature | (-40˚C - 90˚C ) (-40˚C - 90˚C ) | More |
Underfrequency Dropout for Source 1 and Source 2 | 45 - 59.9 Hz 45 - 59.9 Hz | More |
Underfrequency Restore for Source 1 and Source 2 | 45 - 59.5 Hz 45 - 59.5 Hz | More |
Undervoltage Dropout for Source 1 and Source 2 | 75-99% of nominal 75-99% of nominal | More |
Undervoltage Restore for Source 1 and Source 2 | 85-100% of nominal 85-100% of nominal | More |
Voltage Unbalance for Restore for Source 1 and Source 2 | 4 to 19% of nominal 4 to 19% of nominal | More |
Voltage Unbalance on Dropout for Source 1 and Source 2 | 5 to 20% of nominal 5 to 20% of nominal | More |