Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

MX350 ControllerStandard Equipment

Status LEDS for:
  • Source 1 and 2 Availablity
  • Source 1 and 2 Connected
  • Transfer Inhibit
  • Active Alarms
  • Time Delay Active

Graphical Display:
  • Color graphical display with USB Calibration/programming port and Embedded Help
  • Displays 256 time-tagged events with 1 ms resolution
  • Provided detailed outage,test,and diagnostic reports
  • Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation

Ranges of Controls / Metering:
  • Neutral, Engine Start, and Engine stop time delay timers
  • Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
  • Synchroscope
  • Programmable generator exerciser
  • Source 1 and Source 2 In-phase monitor

Testing and Certification
  • Tested in accordance with:
    IEC 60068-2-30
    IEC 60068-2-1
    IEC 60068-2-2
    IEC 60255-22-1
    IEC 60255-22-2
    IEC 60255-22-3
    IEC 60255-22-4
    IEC 60255-22-5
    IEC 60255-22-6
    IEC 60255-25
    IEC 60529; IP54 (front),IP20(back)
    IEC 6100
  • Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
  • Quality System:
    Manufactured under an ISO 9001 Registered Program

MX350 ControllerOptional Equipment

Option Package A:
  • Full function ATS control with full sensing and control capabilities
  • Expanded diagnostics, high-speed 256 event capture, 365 days
  • Monitoring Software (local or remote), USB interface for uploading and downloading setup parameters
  • Four (4) programmable inputs and four (4) outputs assignable to additional ATS features
  • Full complement of programmable ATS control switches AUTO / MAN, Preferred Source selector,Commit / No Commit Xfer, Transition Mode Select for Closed Transition switch models)

Option Package B:
  • Includes Option Package A features, plus
  • Ten (10) customer programmable digital and ten (10)analog alarms.
  • Twenty (20) channel data logger, customer configurable sample period from one (1) cycle to sixty (60) minutes.
  • Waveform capture, ten (10) channels, up to 256 cycles each sixteen (16) samples / sec.
  • Auto Load Shed with voltage, frequency and kW triggers.

Option Package C:
  • Includes Option B features, plus
  • Four (4) additional inputs and outputs (totaling eight (8) in & eight (8) out)

Option Package D:
  • Includes Option Package C features, plus
  • Four (4) additional inputs and outputs (totaling twelve (12) in & twelve (12) out)
  • Customized user control logic

Option Package M:
  • Configuration for Manual Operation only (Non-Automatic)

Overview

The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.

Controller Specifications

Units:
Communications Interface - Optional Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) Less
Control Power 120 VAC 120 VAC Less
Delay NeutralTransition Time Delays (DT,DW) 0-10 minutes 0-10 minutes Less
Delay Transfer to Nonpreferred Source (W) 0-5 minutes 0-5 minutes Less
Delay for Engine Cool Down (U) 0-60 minutes 0-60 minutes Less
Load Control Relay Contacts (1) rated for 10A @ 24VDC or 120VAC rated for 10A @ 24VDC or 120VAC Less
Load Control Relay Contacts (2) 0-259 minutes 0-259 minutes Less
Operating Temperature Ambient (-20˚C to 50˚C) (-20˚C to 50˚C) Less
Overfrequency Dropout for Source 1 and Source 2 50.1 - 63 Hz 50.1 - 63 Hz Less
Overfrequency Restore for Source 1 and Source 2 50 - 62.9 Hz 50 - 62.9 Hz Less
Overvoltage Dropout for Source 1 and Source 2 105 - 110% of nominal 105 - 110% of nominal Less
Overvoltage Restore for Source 1 and Source 2 103 - 108% of nominal 103 - 108% of nominal Less
Source Sensing 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) Less
Storage Temperature (-40˚C - 90˚C ) (-40˚C - 90˚C ) Less
Underfrequency Dropout for Source 1 and Source 2 45 - 59.9 Hz 45 - 59.9 Hz Less
Underfrequency Restore for Source 1 and Source 2 45 - 59.5 Hz 45 - 59.5 Hz Less
Undervoltage Dropout for Source 1 and Source 2 75-99% of nominal 75-99% of nominal Less
Undervoltage Restore for Source 1 and Source 2 85-100% of nominal 85-100% of nominal Less
Voltage Unbalance for Restore for Source 1 and Source 2 4 to 19% of nominal 4 to 19% of nominal Less
Voltage Unbalance on Dropout for Source 1 and Source 2 5 to 20% of nominal 5 to 20% of nominal Less

Technical Summary

Rating Range Switch Dependent Switch Dependent Less
Switch Type Application Dependent Application Dependent Less
Transfer Type Application Dependent Application Dependent Less

Features and Benefits