XQC1600Standard Equipment

Cat 3516C-HD Heavy Duty Diesel Engine
  • Heavy duty, dual element, PowerCore air cleaners with service indicators
  • Triple, primary fuel filters with water separators and bypass valves for on-the-fly filters changes
  • Secondary fuel filters on engine
  • Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil.
  • Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
  • Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
  • Fuel cooler and electric fuel priming pump
  • Electronic differential pressure monitoring of all filters
  • Electronic ADEM™ A4 engine controls
  • Dual 24V electric starting motors

SR-5 Generator
  • Double-bearing, 1844-frame, SR-5 generator with anti-condensation space heaters (1.2 kW, 480V)
  • Brushless, form-wound, permanent magnet excited, three-phase, 4-lead design
  • Class H insulation operating at Class F temperature for extended life
  • Cat Integrated Voltage Regulator (Cat IVR)
  • Stator winding and bearing temperature detectors monitored by RTD module
  • Metallic mesh generator air inlet filters (2)
  • System 4 insulation protection

40' ISO high cube container
  • 9-High stackable, CSC certified
  • Sound attenuated, hinged, radiator intake louvers
  • Sound attenuated package air intake louvers with foldable awnings
  • Five (5) lockable personnel doors with panic releases
  • Interior walls and ceilings insulated with 100 mm of acoustic paneling
  • Side bus bar access door with external access load cable connections
  • Shore power via distribution block connections for jacket water heater, battery charger, space heaters, and generator anti-condensation heaters
  • Six (6) DC lights with 60-min timer
  • Single-wall, 946-L (250gal) fuel tank; certified to BS799-5
  • Solenoid fuel fill control valve for automated filling
  • Sound attenuated to 75 dB(A) (50Hz) 81 dB(A) (60Hz) at 7m (23 ft)
  • Four (4) 1400-CCA, Group 4D, maintenance-free batteries, and 50A battery charger
  • Insulated exhaust silencer with 1.8-m (6ft) stainless steel exhaust stack for increased site power density
  • Engine vibration isolators
  • Easy drain access to standard fluids
  • Standard Cat decals (Optional) and painted Cat Power Module White

Cooling
  • Cooling package provides 49°C (120°F) ambient capability (50 & 60 Hz) at IPP Ratings @ 750m (2,460 ft)
  • Vertical, non-stacked radiator cores with dimpled fins and vertical air discharge
  • Variable frequency fan drive with smart fan control
  • Cat Extended Life Coolant

Generator Controls and Protection
  • EMCP 4.3 generator set controller
  • Automatic start/stop with cool down timer
  • Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
  • AGC-4 provides voltage and frequency adjust, base load / PF / load sharing / synchronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level indications & alarms, fuel tank fuel transfer control
  • Reverse compatibility for interface to legacy power modules
  • 100 kAIC, 4000A-frame generator circuit breaker with LSIG trip unit
  • Multi-mode operation (Island (kW/kVAR sharing, Auto Mains Failure, Peak Shaving, Base Load Power, Export, zero power transfer, power management with multiple units)
  • Manual and automatic paralleling capability
  • Metering Display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchroscope

Quality
  • Factory testing of complete power module
  • CE Certified, NEMA, ISO and IEEE standards
  • OΜ manuals