The ATC-100 is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels.The ATC provides both fixed and jumper-selectable settings to allow for a range of applications. It operates from all system voltages between 120 and 480 Vac, single-phase and three phase at 50 or 60 Hz. The ATC-100 monitors the condition of the three-phase line to line voltage and the frequency of both the utility and generator power sources. It can also be set up for single-phase operation. The ATC-100 provides the necessary intelligence to ensure that the transfer switch operates properly through a series of selectable sensing and timing functions.
Input Control Voltage | 95 to 145 Vac 50/60 Hz 95 to 145 Vac 50/60 Hz | More |
Voltage Measurements of Utility | VAB generator VAB VBC generator VBC VCA generator VCA VAB generator VAB VBC generator VBC VCA generator VCA |
More |
Voltage Measurement Range | 0 to 575 Vac rms (50/60 Hz) 0 to 575 Vac rms (50/60 Hz) | More |
Voltage Measurement Accuracy | ± 1% of full scale ± 1% of full scale | More |
Frequency Measurements Of | Generator Generator | More |
Frequency Measurement Range | 40 Hz to 70 Hz 40 Hz to 70 Hz | More |
Frequency Measurement Accuracy | ±0.3 Hz over the measurement range ±0.3 Hz over the measurement range | More |
Undervoltage Dropout | 80% of the nominal system voltage 80% of the nominal system voltage | More |
Undervoltage Pickup | 90% of the nominal system voltage 90% of the nominal system voltage | More |
Underfrequency Dropout Range | 90% of the nominal system frequency 90% of the nominal system frequency | More |
Underfrequency Pickup Range | 95% of the nominal system frequency 95% of the nominal system frequency | More |
Overfrequency Dropout Range | 115% of the nominal system frequency 115% of the nominal system frequency | More |
Overfrequency Pickup Range | 110% of the nominal system frequency 110% of the nominal system frequency | More |
Operating Temperature Range | –20 to +70°C (–4 to +158°F) –20 to +70°C (–4 to +158°F) | More |
Storage Temperature Range | –30 to +85°C (–22 to +185°F) –30 to +85°C (–22 to +185°F) | More |
Operating Humidity | 0 to 95% relative humidity (noncondensing) 0 to 95% relative humidity (noncondensing) | More |
Operating Environment | Resistant to ammonia, methane, nitrogen, hydrogen and hydrocarbons Resistant to ammonia, methane, nitrogen, hydrogen and hydrocarbons | More |
Generator Start Relay | 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load | More |
K1, K2 Relays | 10A, 1–3 hp @ 250 Vac 10A@30 Vdc 10A, 1–3 hp @ 250 Vac 10A@30 Vdc |
More |
Applicable Testing | UL-recognized component UL 1008, UL 991 Environmental IEC 61000-4-2, 61000-4-3, 61000-4-4, UL-recognized component UL 1008, UL 991 Environmental IEC 61000-4-2, 61000-4-3, 61000-4-4, |
More |
Applicable Testing Continued | 61000-4-5, 61000-4-6, 61000-4-11 CISPR 11, Class B FCC Part 15, Class B CSS 22.2-178 61000-4-5, 61000-4-6, 61000-4-11 CISPR 11, Class B FCC Part 15, Class B CSS 22.2-178 |
More |
Enclosure Compatibility | NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-100 faceplate NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-100 faceplate |
More |
Caterpillar offers a comprehensive variety of electric power systems, customized to fit your needs. Our specialized systems deliver high power and performance in industries across the globe. With Caterpillar, you get outstanding manufacturing quality, expert support, and the essential tools and applications to complete any project.
Learn More About Electric PowerCat generator sets provide a complete factory-built solution with fully featured standard and advanced controls. Optional accessories enhance the capabilities of the genset package-mounted control system.
Learn MoreExplore valuable resources for generator sizing, specification, and training materials. SpecSizer evaluates load types, collects data, and organizes it to help you select the generator set that's best for you. Find product comparisons, technical data, product sizing, and more using our technical information portal (TIP) specifically created for consultants, architects, engineers, and owners.