Electric Power Generation G3512 1000 ekW G3512 1000 EKW

Gas Standby Rating
1000 ekW @ 0.8pf
1000 ekW @ 0.8pf
Fuel Type
Natural Gas
Natural Gas
Emissions/Fuel Strategy
U.S. EPA Certified for Non-Emergency Stationary Genset
U.S. EPA Certified for Non-Emergency Stationary Genset

Product Specifications for G3512 1000 ekW

Generator Set Specifications

Engine Specifications

Generator Set Dimensions

G3512 1000 ekW Standard Equipment

Air Inlet

  • Two-element single-stage air cleaner with enclosure and service indicator
  • Dual air cleaners, 1 per side, with service indicator

Control Panel

  • EMCP 4.3

Cooling System

  • Engine driven pumps for jacket water and separate circuit aftercooler

Cooling

  • Package mounted radiator
  • Jacket water and SCAC engine-driven pumps
  • Jacket water and SCAC thermostats
  • LH or RG connections when radiator is not selected

Exhaust

  • Dry exhaust manifolds, insulated and shielded
  • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
  • Cat-flanged face outlet on turbocharger

Fuel

  • NOx sensor based air-fuel-ratio control
  • Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
  • Gas Train: NFPA37 and CSA B149.3
  • 0.5 to 5 psi engine fuel inlet pressure

Fuel System

  • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
  • Engine-installed electronic control valve
  • Throttle plate, 24V DC actuator, controlled by GECM
  • 24V DC energized-to-run (ETR) gas shutoff valve
  • Gas pressure regulator

General

  • Operation and maintenance manuals
  • Paint- Caterpillar Yellow except rails and radiators gloss black 
  • Parts book
  • “Stationary Use Only” Label in Correspondence with EPA Nonroad Mobile SI rule 
  • RH Service
  • Crankshaft vibration damper and guard

Lubrication

  • Cartridge style oil filter
  • Gear type lube oil pump

Starting/Charging

  • Jacket water heater
  • Battery with cables and rack (shipped loose)
  • Electric Starter
  • Batteries with rack and cables
  • 24V DC starting motors

Generator

  • NEMA Class H insulation
  • Permanent Magnet Excitiation
  • SR5
  • Anti-condensation space heater
  • Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
  • Winding temperature detectors

Governing System

  • ADEM A4

Ignition System

  • Electronic Ignition System (controlled by ADEM A4) 
  • Individual Cylinder Detonation Sensitive Timing (DST) 

Governing

  • ADEM A4 speed governor with 4 to 20ma (0V to 5V) speed input

G3512 1000 ekW Optional Equipment

Air Inlet

  • Mounting brackets and piping
  • Air cleaner with precleaner

Control Panel

  • Local PC monitoring
  • Engine failure relay
  • Remote PC monitoring
  • Local alarm module
  • Remote annunciator

Cooling

  • Remote radiator for JW and SCAC circuits, level switch included but not wired
  • Inlet/Outlet connections
  • Coolant level drain line with valves, fan with guard

Circuit Breakers

  • 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
  • Frame mounting
  • S LSI, G LSIG, P LSIG-P, 4th Digit Type
  • Right, left, rear mounted
  • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
  • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
  • EMCP 4.3
  • 3-pole (IEC 947-2 rated)
  • 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers

Exhaust

  • 305 mm (12 in.) flange
  • Flexible fittings
  • 18, 25 dBA Attenuation
  • 305 mm (12 in.) muffler
  • 305mm (12 in) spark arresting muffler
  • 305 mm (12in.) elbow

Fuel System

  • 3, 0-100 kPag, 4-20mA gas train pressure sensors

General

  • US AID emblem
  • Special paint order
  • Digital diagnostic tool
  • Tool set

Generator

  • Generator air filter
  • European bus bars
  • Low voltage extension box
  • Cable access box
  • Bearing temperature detectors

Starting/Charging

  • 20A, 24VDC battery charger
  • 24V starting motors
  • 45A, 24V charging alternator (requires engine driven pumps)

See how G3512 1000 ekW compares against frequently compared products.

Tools And Expert Help At Every Turn

Why Choose Cat® Electric Power?

Caterpillar offers a comprehensive variety of electric power systems, customized to fit your needs. Our specialized systems deliver high power and performance in industries across the globe. With Caterpillar, you get outstanding manufacturing quality, expert support, and the essential tools and applications to complete any project.

Learn More

EMCP 4 Generator Set Controls

Cat generator sets provide a complete factory-built solution with fully featured standard and advanced controls. Optional accessories enhance the capabilities of the genset package-mounted control system.

Learn More

Application Center

Explore valuable resources for generator sizing, specification, and training materials. SpecSizer evaluates load types, collects data, and organizes it to help you select the generator set that's best for you. Find product comparisons, technical data, product sizing, and more using our technical information portal (TIP) specifically created for consultants, architects, engineers, and owners.

Learn More

Product Brochures and More Are Ready to Download!

Caterpillar product brochures and other informational documents are available for your growing business. To get exclusive access to more awesome content, sign up below. Or for instant access, you can skip this form.


Check out current offers for the G3512 1000 ekW

View More Offers