C18 (50 Hz) India Market Only

< Back

Financing & Insurance
See our Offers
View Product Downloads
Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

C18 (50 Hz) India Market Only Standard Equipment

Cooling System
  • Radiator

Exhaust System

Power Termination
  • Busbar

Control Panel
  • TCP 1000
  • Local design and source

General
  • Paint - Caterpillar yellow except rails and radiators gloss black

C18 (50 Hz) India Market Only Optional Equipment

Air Inlet System

Control Panel

Overview

Producing reliable power from 600 - 600 kVA at 50 Hz, our C18 diesel generator sets are made to meet your standby and prime applications. Each is designed to ISO 8528-5 transient response requirements and built accept 100 percent rated load in one step. Our C18 generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certified. Seismic certification is also available for select models, so you can deliver power despite disturbances. Our integrated control system, including ATS and switchgear ensure a consistent power supply and connection to your fleet through on-site and remote monitoring options. We offer a wide range of EMCP 4 control panel options, with a simple screen display, consolidating all your management and diagnostics tools. The EMCP 4.4 controller provides on package paralleling capability, allowing you to use multiple generator sets to power your facility, providing added capacity and redundancy. We've made our generator sets adaptable to your demands with a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit your spatial restrictions and environmental conditions. Even choose UL 2200 and CSA certified package options for added safety.

Generator Set Specifications

Units:
Minimum Rating 600 kVA 600 kVA Less
Maximum Rating 600 kVA 600 kVA Less
Voltage 415 Volts 415 Volts Less
Frequency 50 Hz 50 Hz Less
Speed 1500 RPM 1500 RPM Less

Generator Set Configurations

Emissions/Fuel Strategy India CPCB/MoEF India CPCB/MoEF Less

Engine Specifications

Engine Model C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel Less
Bore 145 mm (5.71 in) 145 mm (5.71 in) Less
Displacement 18.13 (1106.36³) 18.13 (1106.36³) Less
Stroke 183 mm (7.2 in) 183 mm (7.2 in) Less
Compression Ratio 18:1 18:1 Less
Aspiration Air to Air Aftercooled Air to Air Aftercooled Less
Governor Type Adem™A4 Adem™A4 Less
Fuel System MEUI MEUI Less

Design Criteria

The generator set meets transient response and block loading steps as per ISO 8528-5.

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
  • Control Panel

    The TCP 1000 is a compact Auto Mains (Utility) Failure Control Module that has been developed to provide an outstanding range of features. Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage, current, & power, the modules will give comprehensive engine and alternator protection.

    Single-Source Supplier

    Fully prototype tested with certified torsional vibration analysis available

    World Wide Product Support

    Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products