Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

Overview

Producing reliable power from 180 to 300 ekW at 60 Hz, our C9 diesel generator sets designed to ISO 8528-5 transient response requirements. All C9 generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards with low fuel consumption.

Generator Set Specifications

Units:
Minimum Rating 180 ekW 180 ekW Less
Maximum Rating 300 ekW 300 ekW Less
Emissions/Fuel Strategy EU Stage IIIA, Low Fuel EU Stage IIIA, Low Fuel Less
Voltage 220 to 480 Volts 220 to 480 Volts Less
Frequency 60 Hz 60 Hz Less
Speed 1800 rpm 1800 rpm Less
Duty Cycle Standby, Prime Standby, Prime Less

Engine Specifications

Engine Model C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel Less
Bore 4.41 in 112.0 mm Less
Stroke 5.87 in 149.0 mm Less
Displacement 537.01 in³ 8.8 l Less
Compression Ratio 16.1:1 16.1:1 Less
Aspiration Air to Air Aftercooled Air to Air Aftercooled Less
Fuel System Hydraulic electronic unit injection Hydraulic electronic unit injection Less
Governor Type Adem™A4 Adem™A4 Less

Generator Set Dimensions

Length - Maximum 157.0 in 3988.0 mm Less
Width - Maximum 47.5 in 1207.0 mm Less
Height - Maximum 73.5 in 1867.0 mm Less

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

Cat® generator set packages have been fully prototype tested, and certified torsional vibration analysis reports are available. The packages are designed to meet the NFPA 110 requirement for loading, and conform to the ISO 8528-5 steady state and transient response requirements.

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

C9 (60 Hz) Standard Equipment

Air Inlet System
  • Air cleaner, light duty with disposable paper filter
  • Turbocharger
  • Air cleaner, light duty with disposable paper filter

Control Panels
  • EMC 4.2
  • EMCP4.4 control panel

Cooling System
  • Radiator and cooling fan with guard
  • Fan drive, battery charging alternator drive
  • Coolant drain line with valve
  • Caterpillar extended life coolant
  • Radiator and cooling fan with guard

Exhaust System
  • Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use; shipped loose
  • Flange for customer; shipped loose
  • Stainless steel exhaust flex, gaskets, rain cap and SAE exhaust

Fuel System
  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank

Generators and Generator Attachments
  • Mandatory option circuit breaker, IEC, 3 pole mounted in powercentre
  • Power centre, IP22
  • Voltage regulator (single phase sensing)
  • 12 leads
  • IP23 protection
  • Segregated low voltage (AC/DC) wiring panel
  • IP23 protection
  • 12 leads

Governing System
  • Cat electronic governor (ADEM A4)
  • Cat electronic governor (ADEM A4)

Lube System
  • Oil cooler
  • Lubricating oil
  • Oil drain valves

Mounting System
  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines

Starting / Charging System
  • 24V battery with rack and cables

General
  • Engine and alternator re-paint, Caterpillar Yellow
  • Engine and alternator re-paint, Caterpillar Yellow

C9 (60 Hz) Optional Equipment

Certifications
  • European certificate for conformance
  • Global certificate fpr CIS

Air inlet system
  • Single element air cleaner

Circuit Breakers
  • 4 Pole (IEC-100% rated) circuit breaker upgrades: 400, 630, 800 and 100 amps

Control Panels
  • Oil temperature displays
  • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; overload shutdown via breaker ; Low fuel level shutdown ; Low fuel level alarm ; Fuel level sensor

Cooling System
  • Radiator duct flange
  • Low coolant temperature alarm

Enclosures
  • Sound attenuated enclosure
  • High ambient sound attenuated enclosure

Exhaust System
  • Mufflers - End in / End out; 10 dBA or 25 dBA attenuation
  • 5 and 6 inch elbow kits
  • 6 inch flange
  • 5 - 6 inch flange adaptor

Fuel System
  • Integral duel wall fuel tank base

Generators and Attachments
  • Permanent magnet generator
  • Oversize, AREP, CIP generators

Mounting System
  • Narrow skid base

Starting / Charging System
  • Battery disconnet switch
  • Jacket water heater
  • 5 Amp single battery charger

Application Centre

Explore valuable resources for generator sizing, specification, and training materials. SpecSizer evaluates load types, collects data, and organises it to help you select the generator set that's best for you. Find product comparisons, technical data, product sizing, and more using our technical information portal (TIP) specifically created for consultants, architects, engineers, and owners.

visit page

Why Choose Cat® Electric Power?

Caterpillar offers a comprehensive variety of electric power systems, customised to fit your needs. Our specialised systems deliver high power and performance in industries across the globe. With Caterpillar, you get outstanding manufacturing quality, expert support, and the essential tools and applications to complete any project.

Learn More About Electric Power

EMCP 4 Generator Set Controls

Cat generator sets provide a complete factory-built solution with fully featured standard and advanced controls. Optional accessories enhance the capabilities of the genset package-mounted control system.

Learn More