                              Input Control Voltage
                             | 
                            
                              65 to 145 Vac 50/60 hZ
                              65 to 145 Vac 50/60 hZ
                             | 
                          
                            | 
                              Voltage Measurements of Utility
                             | 
                            
                              Source 1 VAB  Source 2 VAB Source 1 VAC Source 2 VBC Source 1 VCA  Source 2 VCA
                              Source 1 VAB  Source 2 VAB Source 1 VAC Source 2 VBC Source 1 VCA  Source 2 VCA
                             | 
                          
                            | 
                              Voltage Measurement Range
                             | 
                            
                              0 to 790 VAC rms (50/60 Hz)
                              0 to 790 VAC rms (50/60 Hz)
                             | 
                          
                            | 
                              Voltage Measurement Accuracy
                             | 
                            
                              +/-2% of nominal input voltage
                              +/-2% of nominal input voltage
                             | 
                          
                            | 
                              Frequency Measurements Of
                             | 
                            
                              Source 1 and Source 2
                              Source 1 and Source 2
                             | 
                          
                            | 
                              Frequency Measurement Range
                             | 
                            
                              40 Hz to 70 Hz
                              40 Hz to 70 Hz
                             | 
                          
                            | 
                              Frequency Measurement Accuracy
                             | 
                            
                              +/- 0.1 Hz
                              +/- 0.1 Hz
                             | 
                          
                            | 
                              Undervoltage Dropout
                             | 
                            
                              50% to 90% of nominal voltage
                              50% to 90% of nominal voltage
                             | 
                          
                            | 
                              Undervoltage Pickup
                             | 
                            
                              (Dropout +2%) to 99% of the nominal system voltage
                              (Dropout +2%) to 99% of the nominal system voltage
                             | 
                          
                            | 
                              Underfrequency Dropout Range
                             | 
                            
                              90 to 97% of the nominal system frequency
                              90 to 97% of the nominal system frequency
                             | 
                          
                            | 
                              Underfrequency Pickup Range
                             | 
                            
                              (Dropout +1 Hz) to 99% of the nominal system frequency
                              (Dropout +1 Hz) to 99% of the nominal system frequency
                             | 
                          
                            | 
                              Overfrequency Dropout Range
                             | 
                            
                              103 to 110% of the nominal system frequency
                              103 to 110% of the nominal system frequency
                             | 
                          
                            | 
                              Overfrequency Pickup Range
                             | 
                            
                              101% to (dropout - 1 Hz) of the nominal system frequency
                              101% to (dropout - 1 Hz) of the nominal system frequency
                             | 
                          
                            | 
                              Operating Temperature Range
                             | 
                            
                              -20 to 70 degree C (-4 to +158 degree F)
                              -20 to 70 degree C (-4 to +158 degree F)
                             | 
                          
                            | 
                              Storage Temperature Range
                             | 
                            
                              -30 to 85 degree C (-22 to +185 degree F)
                              -30 to 85 degree C (-22 to +185 degree F)
                             | 
                          
                            | 
                              Operating Humidity
                             | 
                            
                              0 to 95% relative humidity (noncondensing)
                              0 to 95% relative humidity (noncondensing)
                             | 
                          
                            | 
                              Operating Environment
                             | 
                            
                              Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
                              Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
                             | 
                          
                            | 
                              Generator Start Relay
                             | 
                            
                              5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
                              5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
                             | 
                          
                            | 
                              K1, K2 Relays
                             | 
                            
                               10A, 1-3 hp @ 250 Vac 10A@30 Vdc
                               10A, 1-3 hp @ 250 Vac 10A@30 Vdc
                             | 
                          
                            | 
                              Applicable Testing
                             | 
                            
                              UL-recognized component Meets intent of UL 991 & UL 1008 Meets  IEC 1000-4-2, 1000-4-3, 1000-4-4
                              UL-recognized component Meets intent of UL 991 & UL 1008 Meets  IEC 1000-4-2, 1000-4-3, 1000-4-4
                             | 
                          
                            | 
                              Applicable Testing Continued
                             | 
                            
                              1000-4-5, 1000-4-6, 1000-4-11 CISPR 11, Class A FCC Part 15, Class A CSS 22.2-178
                              1000-4-5, 1000-4-6, 1000-4-11 CISPR 11, Class A FCC Part 15, Class A CSS 22.2-178
                             | 
                          
                            | 
                              Enclosure Compatibility
                             | 
                            
                              NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-300+ faceplate
                              NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-300+ faceplate
                             |