D40 C4.4 (60 HZ) | 40 kW Diesel Generator

D40 GC Diesel Generator Sets

Request A Price Find Dealer

Key Specs

Standby Rating
40 ekW
40 ekW
Frequency
60 Hz
60 Hz
Emissions/Fuel Strategy
U.S. EPA Tier 3 Certified
U.S. EPA Tier 3 Certified

Features At A Glance

Displaying 1-6 of 8

Cat Generator Set Package

Cat Generator Set Package

        
  • Cat generator set packages have been fully prototype tested
  •     
  • Meets NFPA 110 loading requirements
  •     
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
M-Frame Alternator

M-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
GCCP 1.2 Control Panel

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System

Cooling System

        
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  •     
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications

Certifications

  • UL 2200 Listed
  • ULC Certification Available

Product Specifications for D40 GC

Standby Rating 40 ekW 40 ekW
Frequency 60 Hz 60 Hz
Emissions/Fuel Strategy U.S. EPA Tier 3 Certified U.S. EPA Tier 3 Certified
Voltage 208 to 600 Volts 208 to 600 Volts
Speed 1800 rpm 1800 rpm
Duty Cycle Standby Standby
Engine Model C4.4, In-line 4, 4-cycle diesel C4.4, In-line 4, 4-cycle diesel
Bore 4.1 in 105 mm
Stroke 5 in 127 mm
Displacement 269 in 4.4 l
Compression Ratio 18.2:1 18.2:1
Aspiration Turbocharged Turbocharged
Fuel System Common Rail Common Rail
Governor Type Mechanical, ADEM™A4 Mechanical, ADEM™A4
Length - Maximum 77.2 in 1962 mm
Width - Maximum 43.3 in 1100 mm
Height - Maximum 48 in 1220 mm
Dry Weight - Genset (maximum) 1847 lb 838 kg

D40 GC Standard Equipment

Air Inlet

  • Standard air filter

Circuit breakers

  • Second circuit breaker box
  • Power terminal strip

Control Panel

  • GCCP 1.2 Control panel

Exhaust System

  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose

Fuel System

  • Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank

Cooling System

  • Caterpillar extended life coolant
  • Radiator and cooling fan with guards
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Radiator stone guard

Governing System

  • Mechanical and electrical governing system - model dependent

Lube System

  • Lubricating oil
  • Oil drain line with valve

Control Panels

  • NFPA110 bundle
  • Fuel level alarm
  • Oil temperature gauge and sender
  • Remote E-stop button
  • Volt free contacts genset run and common alarm
  • Discrete I/O module
  • Audible alarm
  • Ground fault relay
  • Remote annunciator module
  • Overload shutdown via breaker
  • Low coolant level shutdown
  • Fuel level reading
  • Protective devices:
  • Low coolant temperature alarm

General

  • Engine and alternator pre-paint, Caterpillar yellow

Starting/Charging System

  • Batteries
  • 24V battery with rack and cables

Telematics

  • Cat® Product Link™ PL444 cellular

D40 GC Optional Equipment

Certificates

  • IBC seismic and wind Certifications

Charging System

  • Battery charger

Circuit breakers

  • Power terminal strip
  • Second circuit breaker box

Control Panels

  • Ground fault relay
  • Remote annunciator module
  • Remote E-stop button

Enclosures

  • Panel viewing window
  • Sound attenuated enclosure, Level 2
  • External emergency stop

Heating Elements

  • Anti-condensation heater
  • Coolant heater
  • Lube oil sump heater
  • Wiring for canopy space heater
  • Jacket water heater
  • Battery heater

Cooling System

  • Radiator transition flange

Fuel System

  • Emergency vent pipe
  • 24 hrs Integral tank
  • 5 Gallon fill containment

Mounting System

  • Seismic vibration isolators

Exhaust System

  • 10, 25 and 35 dBA silencer systems
  • Overhead silencer mounting kit

Generators

  • Permanent magnet excitation (PMG) generator

See how D40 GC compares against frequently compared products.

Use the comparison tool to compare detailed specs of Cat and competitor models.

Compare All Models

Cat RAM and Condition Monitoring

Observe and manage your fleet from anywhere with Cat RAM, and benefit from real-time monitoring by expert advisors with Condition Monitoring.

Learn More

Maintenance and Repairs

Retain genset value with maintenance, upgrade kits, and repair options that extend lifecycles, optimise performance, and help you control costs.

Learn More

Parts

Shop for genuine and Cat Reman parts online, with access to price, inventory, and 24/7 expert support.

Learn More

Service Agreement (Cat® CVA & LTSA)

Every piece of Cat equipment is designed and built to provide maximum productivity and operating economy throughout its working life. Your Cat dealer can help you maintain that built-in value through a Customer Value Agreement (CVA).

Learn More

Media Gallery

D40 GC Open Set

D40 GC Open Set

D40 GC Open Set

D40 GC Open Set

Enclosure

Enclosure

D40 GC Open Set
D40 GC Open Set
D40 GC Open Set
D40 GC Open Set
Enclosure
Enclosure

360 View
360 View

Virtual Tour

Take the interactive virtual product tour to explore the great features and benefits of the D40 GC.

Start Tour
close

Check out current offers for the D40 GC

View More Offers
warning

Internet Explorer users may experience issues with certain features of our site.
Please try a current version of an alternate browser (i.e. Google Chrome, Microsoft Edge, Mozilla Firefox) for the full Cat.com experience.