Input Control Voltage |
65 to 145 Vac 50/60 hZ
65 to 145 Vac 50/60 hZ
|
Voltage Measurements of Utility |
Source 1 VAB Source 2 VAB Source 1 VAC Source 2 VBC Source 1 VCA Source 2 VCA
Source 1 VAB Source 2 VAB Source 1 VAC Source 2 VBC Source 1 VCA Source 2 VCA
|
Voltage Measurement Range |
0 to 790 VAC rms (50/60 Hz)
0 to 790 VAC rms (50/60 Hz)
|
Voltage Measurement Accuracy |
+/-2% of nominal input voltage
+/-2% of nominal input voltage
|
Frequency Measurements Of |
Source 1 and Source 2
Source 1 and Source 2
|
Frequency Measurement Range |
40 Hz to 70 Hz
40 Hz to 70 Hz
|
Frequency Measurement Accuracy |
+/- 0.1 Hz
+/- 0.1 Hz
|
Undervoltage Dropout |
50% to 90% of nominal voltage
50% to 90% of nominal voltage
|
Undervoltage Pickup |
(Dropout +2%) to 99% of the nominal system voltage
(Dropout +2%) to 99% of the nominal system voltage
|
Underfrequency Dropout Range |
90 to 97% of the nominal system frequency
90 to 97% of the nominal system frequency
|
Underfrequency Pickup Range |
(Dropout +1 Hz) to 99% of the nominal system frequency
(Dropout +1 Hz) to 99% of the nominal system frequency
|
Overfrequency Dropout Range |
103 to 110% of the nominal system frequency
103 to 110% of the nominal system frequency
|
Overfrequency Pickup Range |
101% to (dropout - 1 Hz) of the nominal system frequency
101% to (dropout - 1 Hz) of the nominal system frequency
|
Operating Temperature Range |
-20 to 70 degree C (-4 to +158 degree F)
-20 to 70 degree C (-4 to +158 degree F)
|
Storage Temperature Range |
-30 to 85 degree C (-22 to +185 degree F)
-30 to 85 degree C (-22 to +185 degree F)
|
Operating Humidity |
0 to 95% relative humidity (noncondensing)
0 to 95% relative humidity (noncondensing)
|
Operating Environment |
Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
|
Generator Start Relay |
5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
|
K1, K2 Relays |
10A, 1-3 hp @ 250 Vac 10A@30 Vdc
10A, 1-3 hp @ 250 Vac 10A@30 Vdc
|
Applicable Testing |
UL-recognized component Meets intent of UL 991 & UL 1008 Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
UL-recognized component Meets intent of UL 991 & UL 1008 Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
|
Applicable Testing Continued |
1000-4-5, 1000-4-6, 1000-4-11 CISPR 11, Class A FCC Part 15, Class A CSS 22.2-178
1000-4-5, 1000-4-6, 1000-4-11 CISPR 11, Class A FCC Part 15, Class A CSS 22.2-178
|
Enclosure Compatibility |
NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-300+ faceplate