Factory programming will load all standard features and customer-specified options per the default settings.
                                
                            
                            
                            
                        
 
                     
                
                    
                        
                            
                                
                                
                            
                            
                            
                                
                                    In-phase monitor is a feature that will allow a transfer between two sources only when the phase difference between the two sources is near zero. This is an open transition transfer that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
                                
                            
                            
                            
                        
 
                     
                
                    
                        
                            
                                
                                
                            
                            
                            
                                
                                    Load voltage decay transfer is a feature that, after opening the switch for the original source, holds in the neutral position until the voltage on the load is less than 30% of rated voltage. This operation is an open transition that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.