< Back

Project Financing
See our Offers
View Product Downloads
Yes, I would like to receive future marketing communications (such as email) from Caterpillar Inc., its affiliates and subsidiaries worldwide and the Caterpillar dealer network. Regardless of whether you decide to receive these marketing communications, Caterpillar will continue to send service/transactional messages, including those that have to do with any accounts that you may have with us.

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications

Units:
Minimum Rating 680 kVA 680 kVA Less
Maximum Rating 900 kVA 900 kVA Less
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption Less
Voltage 380 to 415 Volts 380 to 415 Volts Less
Frequency 50 Hz 50 Hz Less
Speed 1500 rpm 1500 rpm Less
Duty Cycle Standby, Prime Standby, Prime Less

Engine Specifications

Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel Less
Bore 5.4 in 137.2 mm Less
Stroke 6.0 in 152.4 mm Less
Displacement 1648.86 in³ 27.02 l Less
Compression Ratio 13:01 13:01 Less
Aspiration TA TA Less
Fuel System Pump and Lines Pump and Lines Less
Governor Type ADEM™ A5 ADEM™ A5 Less

Generator Set Dimensions

Length - Maximum 162.4 in 4125.0 mm Less
Width - Minimum 75.0 in 1906.0 mm Less
Width - Maximum 78.3 in 1989.0 mm Less
Height - Maximum 75.0 in 1906.0 mm Less
Dry Weight - Genset (minimum) 12039.0 lb 5461.0 kg Less
Dry Weight - Genset (maximum) 13030.0 lb 5910.0 kg Less

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • EU Certification of Conformance (CE)
  • EEC Declaration of Conformity

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

3412C (50 Hz) Standard Equipment

Air Inlet System
  • Air cleaner, single element canister type with service indicator

Control Panel
  • EMCP 4.2B
  • Customer data link (Modbus RTU)
  • 2 programmable relay outputs (Form C)
  • Features:
  • Voltage adjust
  • Failure to start (overcrank)
  • Volts (L-L & L-N)
  • Reverse power (kW) (32)
  • Accessory module data link
  • Over / under voltage (27 / 59)
  • Speed adjust
  • Low coolant temperature
  • Oil pressure (psi, kPa or bar)
  • Environmental sealed front face
  • Generator temperature monitoring module
  • DC volts
  • Serial annunciator module data link
  • Reverse reactive power (kVAr) (32RV)
  • Amps (per phase & average)
  • High coolant temperature
  • 24-volt DC operation
  • Communications
  • Power Factor (per phase & average)
  • Compatible with the following optional modules:
  • Low coolant level
  • Text alarm / event descriptions
  • Digital I/O module
  • 6 programmable digital inputs
  • Low oil pressure
  • Remote Serial annunciator
  • Engine cycle crank
  • Local annunciator
  • Digital indication for:
  • Over / under Frequency (81 o/u)
  • Generator phase sequence
  • Emergency stop
  • kVAr (per phase, average & percent)
  • Run / Auto / Stop Control
  • Operating hours
  • kVA (per phase, average & percent)
  • Warning / shutdown with common LED indication of shutdowns for:
  • Emergency stop pushbutton
  • Frequency (Hz)
  • coolant temperature
  • Overspeed
  • 4 programmable relay outputs (Form A)
  • kW-hr (total)
  • 2 programmable digital outputs
  • Remote CAN annunciator
  • Overcurrent (50 / 51)
  • kW (per phase, average & percent)
  • RPM
  • Programmable protective relaying functions:

Cooling System
  • Radiator with guard (Sized for 50 degrees C)
  • Coolant level shutdown
  • Coolant drain line with valve, piped to edge of base
  • Fan and belt guards
  • Caterpillar Extended Life Coolant

Exhaust System
  • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose

Fuel System
  • Primary and secondary fuel filters
  • Fuel priming pump
  • Flexible fuel lines terminated on base
  • Water seperator

Generator and Attachments
  • 2:1 Volts/Hz
  • Bus bar termination
  • 3-phase sensing
  • Class H insulation
  • Reactive droop
  • VR6 Voltage Regulator
  • SR4B self excited
  • 12 lead
  • Class F temerature rise

Governing System
  • Cat electronic governor

Lube System
  • Oil drain line with valve, piped to edge of base
  • Lubricating oil
  • Oil filter
  • Fumes disposal, piped to front of radiator

Mounting System
  • Base, formed steel with linear vibration isolators between base and engine-generator

Starting / Charging System
  • 45 amp charging alternator
  • Battery with rack, cables
  • Fuel shutoff solenoid
  • 24 volt starting motor

3412C (50 Hz) Optional Equipment

Air Inlet System
  • Heavy duty air cleaners
  • Duel element air cleaners
  • Open element air cleaners

Circuit breakers
  • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
  • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip

Control Panel
  • Generator temperature monitoring package
  • EMCP 4.4
  • First local annunicators
  • Vandal proof panel door
  • Remote custom annunicators
  • EMCP 4.3
  • Local discrete I/O package
  • Common alarm / shutdown relay
  • Ground fault relay
  • Generator running VFC

Cooling System
  • Radiator duct flange
  • Jacket water heaters

European Certifications
  • Eurasian conformity (EAC) mark

Exhaust System
  • Through wall installation kit
  • Mufflers
  • Manifold and turbocharger guard
  • Elbow kit

Generator and Attachments
  • Permanent magnet excitation
  • Space heater
  • Digital voltage regulator
  • Oversize and premium generators

Lube System
  • Manual sump pump

Mounting System
  • Fuel tank base (1200 ltr)

Special Tests / Reports
  • PGS test report @ 0.8 power factor
  • PGS test report @ 1.0 power factor

Starting / Charging
  • Oversize batteries
  • Battery chargers
  • Battery disconnect switch
  • Heavy-duty starting system

Governing System
  • Electronic load share

Application Centre

Explore valuable resources for generator sizing, specification, and training materials. SpecSizer evaluates load types, collects data, and organises it to help you select the generator set that's best for you. Find product comparisons, technical data, product sizing, and more using our technical information portal (TIP) specifically created for consultants, architects, engineers, and owners.

visit page

Why Choose Cat® Electric Power?

Caterpillar offers a comprehensive variety of electric power systems, customised to fit your needs. Our specialised systems deliver high power and performance in industries across the globe. With Caterpillar, you get outstanding manufacturing quality, expert support, and the essential tools and applications to complete any project.

Learn More About Electric Power

EMCP 4 Generator Set Controls

Cat generator sets provide a complete factory-built solution with fully featured standard and advanced controls. Optional accessories enhance the capabilities of the genset package-mounted control system.

Learn More